To restart the Intelligent Logger in the Helium Compressor Shed:
1. Launch the Hyperware-II software (from Logic Beach)
2. Select "Logger->Connection"
3. In the pop-up, select the "Compressor" logger name and click 'Connect'
4. On the picture of the Logger, click the STOP radio button
5. It may take a few clicks... When the pop-up shows up to confirm, confirm.
6. On the picture of the Logger, click the ENABLE radio button
7. Click the icon for 'Probe Point Values' and wait for the pop-up to update with current values. If the values are updated, the logger is running again.
8. Close the pop-up of Probe Point Values
9. On main menu, do "Logger->Logger Connection" again, then click "Disconnect"
10. Exit Hyperware